Residual Current Circuit Breakers FI, NFI
With a residual current circuit breaker (RCCB) the following protective measures are available: fault protection, protection against fire and additional protection in case of direct contact.
FEATURES:
-
Additional colour display of the position of main contacts (red – contacts closed, green – contacts open)
-
A terminal shape prevents connection of a conductor outside the connection area
-
Type A (designated NFI) – sensitive to alternating and pulsating dc residual operating currents
-
Type AC (designated FI) – sensitive only to alternating residual operating currents of a sine wave form
-
Type F (designated NFIF) – tripping is ensured as for type A and in addition for residual currents with mixed frequencies that can result from single-phase electrical loads with frequency inverters.
-
Type B (designated NFIB) – tripping is ensured as for type A and in addition for smooth d.c. residual currents, residual d.c. currents which may result from rectifying circuits and high frequency a.c. residual currents.
-
Type S: A switch with a delayed break enabling selectivity regarding a general type and a short-time delayed type (type G)
connected on the load side
-
Type G: a short-time delayed breaking characteristic (a min. non-actuating period is 10 ms)
-
FIR-FIT combination: It is used for a protection in circuits where operational currents are higher than rated currents of residual current circuit breakers.